GT – 2738 – Remote I/O

8 Points, MOS Relay Output Terminal, 240Vdc, 0.5A

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

Catalog

 

User Manual

Categories: , ,

Description

GT-2738 (8 Points, MOS Relay Output Terminal, 240Vdc, 0.5A)
Output per module 8 points, bi-directional
Indicators 8 green output state
Relay type MOS Relay (solid state relay)
Output voltage range
( load dependent )
240Vac @ 0.5A resistive

240Vdc @ 0.5A resistive

Output delay time
(resistive load)
Max. AC/DC : 240V

OFF to ON : Max. 0.5ms
ON to OFF : Max. 2.5ms

Output current rating Max. 0.5A per channel
Frequency range ( Vac ) 47 ~ 63Hz
Open-state leakage current Max. 40uA
Common type 8 points / 2 COM
General Specification
Power dissipation Max. 130mA  @ 5Vdc
Isolation I/O to Logic : photocoupler isolation
UL field power Supply voltage : 24Vdc nominal, Class 2
Field power Supply Voltage : 24Vdc
Voltage Range : 15 ~ 30Vdc
(AC Power Not Used)
Wiring I/O Cable Max. 0.75mm²(AWG 18)
Weight 63g
Module Size 12mm x 109mm x 70mm

 

Pin No. Signal Description Signal Description Pin No.
0 Output Channel 0 _A Output Channel 0 _B 1
2 Output Channel 1_A Output Channel 1 _B 3
4 Output Channel 2 _A Output Channel 2 _B 5
6 Output Channel 3 _A Output Channel 3 _B 7
8 Output Channel 4 _A Output Channel 4 _B 9
10 Output Channel 5 _A Output Channel 5 _B 11
12 Output Channel 6 _A Output Channel 6 _B 13
14 Output Channel 7 _A Output Channel 7 _B 15
16 Common (Field Power 0V) Common (Field Power 24V) 17