GN-9371 – Programmable I/O (MODBUS)

Programmable Modbus/TCP Network Adapter, Economic Version

G-Series Programmable Adapter Modbus

 

Description

Specifications

Interface Specification, GL-9084 (CC-Link IE Field Basic Network Adapter)

Adapter Type Slave station (CC-Link IE Field Basic Server)
Protocol CC-Link IE Field Basic, SLMP
Sub-Protocol MODBUS/TCP,MODBUS/UDP,HTTP,DHCP,10 TCP Connections
Port number 61450 (CyclicData)
61451 (port number of the slave station of NodeSerch)
Max. Expantsion Module 16 slots
Number of occupied stations 1 stations
Max. Data Size(RX, RY) each 32 bytes (1 Stations occupied)
Max. Data Size(RWr, RWw) each 256 bytes (1 Stations occupied)
Max. link points per station (RX, RY) each 64 points
Max. link points per station (RWr,RWw) each 32 points
Max Length Bus Line Up to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Max. Nodes Limited by Ethernet Specification.
Baud Rate 10/100Mbps, Auto-negotiation, Full duplex
Interface Connector RJ-45 socket * 2pcs
IP-Address Setup Via DHCP/BOOTP or IOGuide(Crevis Software)
IP-Address Range xxx.xxx.xxx.1 ~ 253 (User area)
xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function)
Serial Port RS232 for MODBUS/RTU, Touch Pannel or IOGuide
Serial Configuration (RS232) Node : 1 (Fixed)
Baud Rate : 115200 (Fixed)
Data bit : 8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit : 1 (Fixed)
Indicator 6 LEDs
1 Green/Red, Module Status (MOD)
1 Green, Physical Connection (DLINK)
1 Green, Exchange Data/Traffic Present (RUN/ERR)
1 Green/Red, Expansion I/O Module Statsus (IOS)
1 Green, System Power Status
1 Green, Field Power Status
2 LEDs (each RJ45 Connector)
1 Yellow, Link/Active
1 Green, Not used
Module Location Starter module left side of G-Series system
Field Power Detection About 14Vdc

General Specification

System Power Supply voltage : 24Vdc nominal
Supply voltage range : 16~32Vdc
Protection : Output current limit (Min. 1.5A)
Reverse polarity protection
Power Dissipation Refer to Network Adapter Manual
Current for I/O Module 1.5A @ 5Vdc (When using in ‘60℃ ~ 70℃’ temperature environment,
the power dissipation is limited to 0.8A.)
Isolation System power to internal logic : Non-isolation
System power I/O driver : Isolation
Field Power Supply voltage : 24Vdc typical (Max. 32Vdc)
* Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 10A Max.
Module Size 54mm x 99mm x 70mm