GT – 2328 – Remote I/O

Digital Output, 8 Points, Source(Positive), 24VDC, 0.5A, 10 RTB

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

Catalog

 

User Manual

Description

GT-2328 Output Specification
Output per module8 Points Source type
Indicators (Logic side)8 Green output state
Output Voltage RangeNominal 24Vdc, Min. 15Vdc to Max. 32Vdc
ON-state voltage dropMax. 0.5Vdc @ 25℃, 70℃, -40℃
Field Power OFF-state voltage4.6Vdc @ 25℃
ON-State Min. Current1mA per channel
OFF-State Leakage currentMax. 25uA
Output Signal DelayOFF to ON : 0.3ms maximum
ON to OFF : 0.3ms maximum
Output Current RatingMax. 0.5A per channel / Max. 4A per unit
ProtectionOver Current limit : Min 6.5A@ 25℃ per each channels
Thermal Shutdown : Min 4A@ 25℃ per each channels
Short circuit protection
COMMON Type8 points / Internal 2Com
General Specification
Power Dissipation40mA maximum @ 5.0Vdc
IsolationI/O to Logic : Isolation
Field Power : Non-isolation
Field PowerSupply voltage : 24Vdc nominal
Voltage range : 15 to 32Vdc
Power dissipation: 10mA @ 24Vdc
WiringI/O Cable Max. 2.0mm2(AWG 14)
Weight40g
Module Size12mm x 99mm x 70mm
Pin No.Description
0Output Channel 0
1Output Channel 1
2Output Channel 2
3Output Channel 3
4Output Channel 4
5Output Channel 5
6Output Channel 6
7Output Channel 7
8Common (Field Power 0V)
9Common (Field Power 0V)