16 Channels Universal (Sink or Source) Input Terminal

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

Catalog

 

User Manual

Categories: ,

Description

GT-12DF (16 Channels Universal Input Terminal)
Inputs per module16 Points Universal Digital Type
Indicators16 Green input state
ON–state Voltage24V dc nominal
@70℃ – Min. 15Vdc to Max. 28.8Vdc
@60℃ – Min. 15Vdc to Max. 32Vdc
ON-state current3.05mA maximum/point @32Vdc
Input Signal DelayOFF to ON : 0.3ms Max
ON to OFF : 0.3ms Max
Nominal Input Impedance14.9K ohm typical
COMMON Type16 points / 2 COM (Single Common)
General Specification
Power dissipation50mA maximum @ 5.0Vdc
IsolationI/O to Logic : Photocoupler isolation
Field PowerSupply voltage : 24Vdc nominal
Voltage range : 15~32Vdc
Power dissipation: 0mA @ 32Vdc
WiringI/O Cable Max. 0.75mm²(AWG 18)
Weight63g
Module Size12mm x 109mm x 70mm

 

Pin No.Signal DescriptionSignal DescriptionPin No.
0Input Channel 0Input Channel 11
2Input Channel 2Input Channel 33
4Input Channel 4Input Channel 55
6Input Channel 6Input Channel 77
8Input Channel 8Input Channel 99
10Input Channel 10Input Channel 1111
12Input Channel 12Input Channel 1313
14Input Channel 14Input Channel 1515
16Common(SinkOper.0V /
Source Oper.24V)
Common(SinkOper.0V/
Source Oper.24V)
17