GT-12DF – Remote I/O

16 Channels Universal (Sink or Source) Input Terminal

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

Catalog

 

User Manual

Categories: ,

Description

GT-12DF (16 Channels Universal Input Terminal)
Inputs per module 16 Points Universal Digital Type
Indicators 16 Green input state
ON–state Voltage 24V dc nominal
@70℃ – Min. 15Vdc to Max. 28.8Vdc
@60℃ – Min. 15Vdc to Max. 32Vdc
ON-state current 3.05mA maximum/point @32Vdc
Input Signal Delay OFF to ON : 0.3ms Max
ON to OFF : 0.3ms Max
Nominal Input Impedance 14.9K ohm typical
COMMON Type 16 points / 2 COM (Single Common)
General Specification
Power dissipation 50mA maximum @ 5.0Vdc
Isolation I/O to Logic : Photocoupler isolation
Field Power Supply voltage : 24Vdc nominal
Voltage range : 15~32Vdc
Power dissipation: 0mA @ 32Vdc
Wiring I/O Cable Max. 0.75mm²(AWG 18)
Weight 63g
Module Size 12mm x 109mm x 70mm

 

Pin No. Signal Description Signal Description Pin No.
0 Input Channel 0 Input Channel 1 1
2 Input Channel 2 Input Channel 3 3
4 Input Channel 4 Input Channel 5 5
6 Input Channel 6 Input Channel 7 7
8 Input Channel 8 Input Channel 9 9
10 Input Channel 10 Input Channel 11 11
12 Input Channel 12 Input Channel 13 13
14 Input Channel 14 Input Channel 15 15
16 Common(SinkOper.0V /
Source Oper.24V)
Common(SinkOper.0V/
Source Oper.24V)
17