GN-9284 – Network Adapter

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

 

Catalog

 

User Manual

 

Categories: ,

Description

Interface Specification, GN-9284 (CC-Link IE Field Basic Network Adapter)
Adapter TypeSlave station (CC-Link IE Field Basic Server)
ProtocolCC-Link IE Field Basic, SLMP
Sub-ProtocolMODBUS/TCP,MODBUS/UDP,HTTP,DHCP,10 TCP Connections
Port number61450 (CyclicData)
61451 (port number of the slave station of NodeSerch)
Max. Expantsion Module32 slots
Number of occupied stations1 ~ 4 stations
Max. Data Size(RX, RY)each 32 bytes (4 Stations occupied)
Max. Data Size(RWr, RWw)each 256 bytes (4 Stations occupied)
Max. link points per station (RX, RY)each 64 points
Max. link points per station (RWr,RWw)each 32 points
Max Length Bus LineUp to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Max. NodesLimited by Ethernet Specification.
Baud Rate10/100Mbps, Auto-negotiation, Full duplex
Interface ConnectorRJ-45 socket * 2pcs
IP-Address SetupVia DHCP/BOOTP or IOGuide(Crevis Software)
IP-Address Rangexxx.xxx.xxx.1 ~ 253 (User area)
xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function)
Serial PortRS232 for MODBUS/RTU, Touch Pannel or IOGuide
Serial Configuration (RS232)Node : 1 (Fixed)
Baud Rate : 115200 (Fixed)
Data bit : 8 (Fixed)
Parity bit : No parity (Fixed)
Stop bit : 1 (Fixed)
Indicator6 LEDs
1 Green/Red, Module Status (MOD)
1 Green, Physical Connection (DLINK)
1 Green, Exchange Data/Traffic Present (RUN/ERR)
1 Green/Red, Expansion I/O Module Statsus (IOS)
1 Green, System Power Status
1 Green, Field Power Status
2 LEDs (each RJ45 Connector)
1 Yellow, Link/Active
1 Green, Not used
Module LocationStarter module left side of G-Series system
Field Power DetectionAbout 14Vdc
General Specification
UL System PowerSupply voltage : 24Vdc nominal, Class2
System PowerSupply voltage : 24Vdc nominal
Supply voltage range : 15~30Vdc
Protection : Output current limit (Min. 1.5A)
Reverse polarity protection
Power Dissipation70mA typical @ 24Vdc
Current for I/O Module1.5A @ 5Vdc (When using in ‘60℃ ~ 70℃’ temperature environment,
the power dissipation is limited to 0.8A.)
IsolationSystem power to internal logic : Non-isolation
System power I/O driver : Isolation
UL System PowerSupply voltage : 24Vdc nominal, Class2
Field PowerSupply voltage : 24Vdc typical (Max. 30Vdc)
* Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power ContactDC 10A Max.
Weight162g