Description
Interface Specification, GN-9222 (PROFIBUS Network Adapter) | ||
Redundancy | Not supported | |
Repeater Control Signal | RS-485 Signal | |
Freeze mode | Support | |
Sync mode | Support | |
Auto baudrate | Support | |
Fail safe mode | Support | |
Station type | Slave | |
FMS support | Not supported | |
Max. Network Node | 125 Nodes | |
Max. Expansion Slot | 63 Slots | |
I/O Data Size | Input : 244bytes / Output : 244bytes | |
Indicators | 6 Status LEDs 1 Green/Red, Module Status (MOD) 1 Green/Red, Network Status (NET) 1 Red, Diagnostic Status (DIA) 1 Green/Red Expansion I/O Module Statsus (IOS) 1 Green, System Power Status 1 Green, Field Power Status |
|
Communication Rate | 9.6K ~ 12M (1.2Km~100m) | |
Communication Speed | 9.6 ~ 12000 Kbps (Auto baudrate selection) | |
Bus Connection | 9 Pin D-Sub Connector | |
Other Serial Port | RS232 for MODBUS/RTU, Touch Panel or IOGuide | |
Serial Configuration (RS232) | Node : 1 (Fixed) Baud Rate : 115200 (Fixed) Data bit : 8 (Fixed) Parity bit : No parity (Fixed) Stop bit : 1 (Fixed) |
|
Module Location | Starter module left side of G-Series system | |
Field Power Detection | About 14Vdc | |
General Specification | ||
UL System Power | Supply voltage : 24Vdc nominal, Class2 | |
System Power | Supply voltage : 24Vdc nominal Supply voltage range : 16~30Vdc Protection : Output current limit (Min. 1.5A) Reverse polarity protection |
|
Power Dissipation | 100mA @ 24Vdc | |
Current for I/O Module | 1.5A @5Vdc | |
Isolation | System power to internal logic : Non-Isolation System power I/O driver : Isolation |
|
UL System Power | Supply voltage : 24Vdc nominal, Class2 | |
Field Power | Supply voltage : 24Vdc typical (Max. 30Vdc) * Field Power Range is defferent depending on IO Module series. Refer to IO Module’s Specification. |
|
Max. Current Field Power Contact | DC 10A Max. | |
Weight | 163g | |
Module Size | 54mm x 99mm x 70mm |