GL-9089 – Network Adapter

Main features

– Various type of protocols (MODBUS TCP , EtherNet IP , PROFINET , EtherCAT , CC-Link IE , CC-Link IE Field Basic , DeviceNet , PROFIBUS , MODBUS RS485, CC-Link , CanOpen , BACnet ,MODBUS RTU)

– More than 90 different I/Os (Universal type of Digital Input module, 32 points slice I/O module, ERNI type connector input/output module)

– Space-saving, compact size & slice type for the module expansion

– Easy and convenient working environment for the operator when wiring and install

Catalog

 

User Manual

 

 

Categories: ,

Description

Interface Specification, GL-9089   (MODBUS TCP/UDP NETWORK ADAPTER)
Adapter TypeSlave node (MODBUS/TCP,MODBUS/UDP Server)
ProtocolMODBUS/TCP,MODBUS/UDP,HTTP,DHCP,10 TCP Connections
Sub-Protocol**Ethernet/IP
Max. Expantsion Module16 slots
Max. Input / Output Data SizeMax. Input 256 bytes / Output 256 bytes
Max Length Bus LineUp to 100m from Ethernet Hub/Switch with twisted CAT5 UTP/STP
Max. NodesLimited by Ethernet Specification.
Baud Rate100Mbps, Auto-negotiation, Full duplex
Interface ConnectorRJ-45 socket * 2pcs
IP-Address SetupVia DHCP/BOOTP or IOGuide(Crevis Software)
IP-Address Rangexxx.xxx.xxx.1 ~ 253 (User area)

xxx.xxx.xxx.254 ~ 255 (Reserved for IAP Function)

IAP ModeWhen DIP Switch 1 to 8 setting is 254 or 255

(Using only Internet Explorer / recommended version 11)

Indicator4 LEDs

1 Green/Red, Module Status (MOD)

1 Green, Physical Connection (LINK)

1 Green, Exchange Data/Traffic Present (ACTIVE)

1 Green/Red, Expansion I/O Module Statsus (IOS)

2 LEDs (each RJ45 Connector)

1 Yellow, Link/Active

1 Green, Not used

Module LocationStarter module left side of G-Series system
General Specification
UL System PowerSupply voltage : 24Vdc nominal, Class2
System PowerSupply voltage : 24Vdc nominal

Supply voltage range : 15~28.8Vdc

Protection : Reverse polarity protection

Power Dissipation75mA typical @ 24Vdc
Current for I/O Module1.0A @ 5Vdc
IsolationSystem power to internal logic : Non-isolation
System power I/O driver : Isolation
UL Field PowerSupply voltage : 24Vdc nominal, Class2
Field PowerSupply voltage : 24Vdc typical (Max. 30Vdc)

* Field Power Range is different depending on IO Module series.

Refer to IO Module`s Specification.

Max. Current Field Power ContactDC 8A Max
WiringI/O Cable Max. 2.0㎟(AWG 14)
Torque0.8Nm(7 lb-in)
Weight76g
Module Size22mm x 109mm x 70mm
Environment ConditionRefer to ‘1. Environment Specification’
Pin NoSignal Description
1System Power, 24V
2System Power, Ground
3F.G
4Field Power, Ground
5Field Power, 24V